90kw~115kw Built-In Bypass Soft Starter
NR1000 series 90kW~115kW high-power built-in bypass soft starter is specially developed for heavy-duty high-current 380V three-phase squirrel cage motors, adopting upgraded large-current thyristor module and enhanced heat dissipation air channel structure. This power segment upgrades to 3 independent programmable relay output channels, standard integrated 4-20mA analog monitoring terminal, and strengthens short-circuit breaking…
NR1000 series 90kW~115kW high-power built-in bypass soft starter is specially developed for heavy-duty high-current 380V three-phase squirrel cage motors, adopting upgraded large-current thyristor module and enhanced heat dissipation air channel structure. This power segment upgrades to 3 independent programmable relay output channels, standard integrated 4-20mA analog monitoring terminal, and strengthens short-circuit breaking capacity for high-current industrial equipment. The built-in bypass contactor greatly reduces long-term thyristor heat generation, solving overheating failure risks of high-power soft starters under 24-hour continuous running, widely used in mining, water conservancy and heavy crushing industrial sites.
- 3 Independent Programmable Relay Outputs (AC250V 5A): Support multi-group interlock logic – bypass completion signal, fault alarm, running status, upper/lower current limit feed, delay output (0~240s adjustable), realize multi-equipment linkage control in large central control cabinets
- Upgraded Large-Current Heat Dissipation System: Simulated fluid heat dissipation design, enlarged air cooling channel, adapt to high-temperature workshop environment, capacity derate only 2% per ℃ above 40℃
- Ultra-High Overload Resistance: 400% rated current sustain 60s short-time startup overload, ideal for locked-rotor heavy loads like mining crushers and large slurry pumps
- Standard Integrated 4-20mA + RS485 Dual Interfaces: Real-time upload motor running current to DCS/PLC system, remote parameter modification & fault query via Modbus RTU industrial bus
- Multi-Level Inverse Time Overload Protection (1~6 Curves): Match different high-power motor insulation grades, prevent long-term partial overload burning of expensive large motors
- Instant Emergency Stop Function: Normally closed external emergency stop terminal, support self-recovery mode – auto clear fault signal after external hazard removal, match mining safety production standards
- Full-Process Real-Time Monitoring: Display 3-phase current, input voltage, frequency, phase sequence angle, cumulative running hours, fault record storage on bilingual LCD screen
- Strict Factory Quality Inspection: Each unit passes full-load aging test before delivery, complete nameplate, inspection certificate and warranty card for traceability
| Project Name | Performance Metrics | |
| Scope of application | 3-phase squirrel cage asynchronous motor | |
| Power range | 3kW~22kW (380V mini type), 30kW~400kW (380V conventional type) | |
| Rated voltage | 380V(±20%) | |
| Rated frequency | 50/60Hz ±5% | |
| Overload capacity | ≤22kW: 300% 30 seconds, 120% continuous; >22kW: 400% 60 seconds, 120% continuous | |
| Control power supply voltage | The 380V model does not require an external control power supply | |
| Adjustable current multiplier | 1–5 times | |
| Soft start time | 1 to 90 seconds | |
| Module operation mode | Long-term | |
| Cooling method | Forced air cooling | |
| Secondary interface terminal | Discrete input | 3 routes |
| Relay output | ≤115kW: 1-channel (programmable); >115kW: 3-channel (programmable) | |
| 4-20mA | ≤22kW: None; >22kW: 1 channel (optional) | |
| RS485 | ≤22kW: 1 channel; >22kW: 1 channel (optional expansion) | |
| Protection | Short circuit quick break, overcurrent, overheating protection, inverse time overload, voltage phase loss, phase unbalance, instant stop, undervoltage, overvoltage, underload, startup failure, phase sequence error | |
| Host overload protection | Overload inverse time limit, optional levels 1–6 | |
| Host current imbalance protection | Unbalanced tripping standard: 5-100% for any two phases | |
| Unbalanced trip delay: 1-60 seconds adjustable | ||
| Host short-circuit protection | Quick break time: ≤ 0.1S, adjustable | |
| Bus function | Interface: RS485; Protocol: Modbus RTU | |
| Human-machine interface | 4-line COG screen | |
| Language | Chinese, English | |

| specifications and models | External dimensions (mm) | Installation size (mm) | ||||
| W1 | H1 | D | W2 | H2 | Φ | |
| 5.5KW-22KW | 60 | 165 | 145 | 55 | 155 | m4 |
| 30KW-37KW | 110 | 250 | 162 | 85 | 220 | m5 |
| 45KW-75KW | 140 | 270.5 | 139.5 | 110 | 245 | m6 |
| 90KW-115KW | 210 | 340 | 185 | 210 | 315 | m8 |
| 132KW-200KW | 280 | 610 | 200 | 232 | 540 | m8 |
| 250KW-400KW | 332 | 725 | 246 | 282 | 640 | m10 |